Air Cooler Louver Actuator Assembly

Air Cooler Louver Actuator Assembly

The Air Cooler Louver Actuator Assembly provides powered blade adjustment for industrial air cooler louver systems. An electric actuator drives the blade shaft through a gear set or connecting rod, allowing controlled adjustment of the louver opening for airflow regulation.
Share to
Send Inquiry
Description
Technical Parameters

The Air Cooler Louver Actuator Assembly provides powered blade adjustment for industrial air cooler louver systems. An electric actuator drives the blade shaft through a gear set or connecting rod, allowing controlled adjustment of the louver opening for airflow regulation.

Available power supply options include 24V DC, 110V AC, and 220V AC. With a typical positioning accuracy of ±1° to ±2° and an adjustment range of 0° to 90°, this electric air cooler louver actuator supports controlled airflow adjustment in industrial air-cooled heat exchanger installations.

Technical Specifications

Product Type Electric Air Cooler Louver Actuator Assembly
Drive Type Electric Actuator
Power Supply Options 24V DC / 110V AC / 220V AC
Drive Transmission Gear Set / Connecting Rod
Adjustment Angle 0°–90°
Positioning Accuracy ±1° to ±2°
Adjustment Time 15–60 seconds for 0°–90° adjustment
Position Feedback Feedback Potentiometer / Limit Switch
Control Standard Control Signals
Louver Mechanical Component Materials Magnesium Alloy / Hot-dip Galvanized Carbon Steel
Configuration According to Air Cooler Louver Requirements

Drive and Control Configuration

The electric actuator drives the louver blade shaft through a gear set or connecting rod. This transmission arrangement transfers actuator movement to the louver blades for coordinated angle adjustment.

Three power supply options are available: 24V DC, 110V AC, and 220V AC. Position feedback can be configured through feedback potentiometers or limit switches to confirm the blade position.

The 0°–90° adjustment range and 15–60-second adjustment time provide controlled blade movement for airflow regulation. Electric actuation also eliminates the need for a compressed-air supply at the louver operating location.

Materials and Installation Adaptation

The louver mechanical components are available in magnesium alloy or hot-dip galvanized carbon steel. The external appearance can be customized to fit the air cooler according to non-standard requirements.

The actuator transmission arrangement uses a gear set or connecting rod to drive the blade shaft. The installation configuration is coordinated with the louver structure and available mounting space.

Operating Environment

Electric actuation is suitable for air cooler installations where powered airflow regulation is required without a dedicated compressed-air supply.

For high-humidity or salt-spray environments, actuator seals and connecting rod lubrication require regular inspection. Waterproof or explosion-proof enclosures may be required for corrosive or hazardous operating areas, depending on project conditions.

Manufacturing and Supply

Shandong Jiuyuan Engineering Equipment Co., Ltd. provides air cooler design, manufacturing, installation, renovation, and maintenance services.

Our engineering team works with customers on operating conditions, equipment layouts, and project requirements. Manufacturing facilities include CNC cutting, laser cutting, welding, drilling, and inspection equipment.

For air cooler projects, we coordinate the louver configuration with the associated equipment design and supply requirements.

Request a Quote

Send us your existing air cooler louver drawings, actuator specifications, equipment photographs, or required quantity. Our team can review the drive configuration, power supply, adjustment range, and installation requirements to prepare a suitable quotation for your project.

Hot Tags: air cooler louver actuator assembly, China air cooler louver actuator assembly manufacturers, suppliers, factory

Send Inquiry
Send Inquiry